A minimum A3 Block Plan (for more complex buildings/systems DFES may seek larger-sized plans) prepared using engraved plastic has been fixed within the booster cabinet. For examples of block plans please refer to Figs in accordance with AS2419.1, Section Block Plan.
Booster cabinet signage has been provided in accordance with AS 2419.1 and/or any specified DFES signage requirements, as appropriate.
The hydrant booster location is accessible for DFES appliances and personnel and hardstand installed.
All fire hydrants are accessible at all times. (i.e. vehicles are not obstructing hydrants).
Water discharge will not affect:
- gardens, paving, roads, moving or parked vehicles and other buildings. (i.e. dirty water upon windows).
- trades people or equipment on site.
- the general public in and around the test site.
Water leakage/collection from use of internal fire hose/ hydrants is the responsibility of the builder.